Quick answer: In-wall Ethernet cable must be solid-copper Cat5e or Cat6 with a jacket rated for the space it runs through, which in North America means CMR for risers and CMP for plenum ceilings, and in Europe a reaction-to-fire class. Stranded patch cable must not go inside a wall. Run one cable per outlet back to a central patch panel, keep the untwisted length under 13 mm at each termination, and leave a service loop behind every plate.
Cable behind plasterboard is decided once. The mistakes that matter are cheap to avoid and expensive to correct: using stranded cord, daisy chaining outlets, or pulling Cat5e where a future 10G link was planned. Everything else can be fixed at the ends.
What to pull
Solid conductors and category
Solid copper has lower loss and does not cold-flow under a punch-down terminal. Cat5e is adequate for gigabit and 2.5G; Cat6 is the sensible default for new work; Cat6a, which is usually shielded, is for 10G at full distance or for noisy environments. Copper-clad aluminium is cheaper and worse: it corrodes at the termination and has higher resistance.
Jacket rating
CMR is the usual choice for vertical risers between floors. CMP is required in plenum spaces where air circulates through the ceiling. A cable with no rating is a patch cord and belongs on a desk. The rating is printed on the jacket, so photograph the reel before it goes into the wall.
Installation rules
| Rule | Value | Why |
|---|
| Bend radius | 4 x diameter, 8 x if flexing | Kinks change impedance |
| Distance from mains | 50 mm minimum | Reduces induced noise |
| Support interval | 300 mm horizontal | Weight and strain relief |
| Runs per outlet | One, home run | Ethernet is point to point |
| Service loop | 300 mm at each end | Allows re-termination |
Termination at each end
At the wall, punch the solid cable into a keystone jack and fit a plate. At the centre, punch into a patch panel rather than fitting loose plugs, because a panel gives strain relief, labelling and a test point. Keep the same wiring pattern, T568A or T568B, at both ends, and trim the conductors in the same motion as the punch.
Test before closing anything up. A cheap continuity tester confirms eight conductors, which is not the same as a link that will carry gigabit; a certifier reports length, loss and crosstalk against the category. If that is not available, at least check pair order and length, because a split pair is the fault that hides until someone tries 2.5G.
Fire stopping and inspection
Where the cable passes through a fire-rated wall, the penetration must be sealed with an approved compound or a fire-rated grommet. Expanding foam sold for windows is not a substitute. Keep the cable off ceiling tiles and away from downlight transformers, which run hot and can soften a PVC jacket over years.
A Cat6a cable is worth pulling if the same conduit may later serve 10G, and an Ethernet wall plate with a proper back box keeps the termination protected. If you terminate on site, the RJ45 connector reference covers plug types and the difference between solid and stranded contacts.
Practical scenarios
- Whole-house renovation: two cables to each study and television position, all home run to a utility cupboard, labelled by room at both ends.
- Adding one outlet to a finished room: use surface trunking to the ceiling void rather than chasing plaster, and keep the bend radius at the plate.
- Loft conversion: CMP jacket if the cable crosses a plenum ceiling, and fire-stop the penetration into the stairwell.
- PoE access point in a corridor ceiling: use solid Cat6 and leave a service loop, because the AP will be replaced several times over the cable’s life.
FAQ
Can I use a normal patch cable inside a wall?
No. Stranded conductors have higher loss and cold-flow under terminals, and the jacket is usually unrated for concealed spaces. It may work for years and then fail at the termination, which is exactly the fault that is hardest to find.
Do I need conduit?
Not always, but it makes the installation replaceable. A 20 mm conduit with a pull string costs little during a build and allows a future fiber or Cat6a pull without opening the wall. In masonry walls, conduit is effectively mandatory.
How many cables per room?
Two per desk position and two behind each television is a practical minimum. Cable is cheap compared with the labour of a second visit, and a spare run can carry a phone, an access point or a printer without adding a switch.