Quick Answer / Summary: Cladding is the 125 um glass layer around the core, with a lower refractive index, that keeps light inside by total internal reflection. Cores measure 9 um for singlemode and 50 um or 62.5 um for multimode, while the cladding stays 125 um in all of them. The 250 um coating and the 900 um tight buffer are polymer protection only, and they do not guide a mode. Nothing outside the glass confines light.
Cladding is glass, not a plastic skin. In standard telecom fiber it measures 125 um across, with a refractive index a fraction below the core so light meeting the boundary is reflected back. The coating at 250 um and the buffer at 900 um are polymer layers added after drawing, and neither of them guides light.
The Layer Stack From the Core Out
Five layers sit between the light and the cable tray. Core, cladding, coating, buffer and jacket each do one job, and a fault blamed on the wrong layer sends the installer to the wrong fix.
Core and Cladding
The core carries the mode field and the cladding confines it. Singlemode uses a 9 um core with a small index step; multimode uses 50 um or 62.5 um with a graded profile. Both keep the same 125 um cladding so one cleaver and one connector family serve either type.
Coating and Buffer
The coating is a 250 um acrylate applied during drawing, and it protects the glass from abrasion and moisture. The tight buffer at 900 um is the plastic layer that makes a single fiber handleable and crimpable inside a patch cord.
Why 125 um Is Fixed
The dimension is a standard rather than an accident. Cleavers, splice holders, ferrules and alignment sleeves are all built around 125 um, which is why a 50 um core and a 9 um core both use an LC connector with a 1.25 mm ferrule.
Alignment Tolerance
A 9 um core inside a 125 um cladding means a 1 um offset is a large fraction of the mode field. The ferrule aligns the cladding, so a cladding diameter outside tolerance shifts the core even when the connector looks fully seated.
Cleave and Polish
Cleaving scores the glass and breaks it along a plane, then polishing shapes the endface. Both operations reference the cladding, so a fiber stripped to the wrong diameter will cleave badly even when the tool is set correctly.
Layer Dimensions and Jobs
Read the diameter column as the outside dimension of each layer, not of the glass alone.
Where Buyers Mix Them Up
Two mistakes recur. A 900 um buffer is quoted as a cladding dimension, so the buyer expects a 900 um ferrule. A 250 um coating is quoted as cladding, so the installer strips to 250 um and wonders why the cleave is ragged. Both come from skimming a datasheet column.
Why the Confusion Costs Money
A wrong diameter assumption reaches the field as a failed termination batch, and every connector in that batch has to be cut off and redone. The glass is fine. The specification quoted to the installer was not.
| Layer | Diameter | Material | Job | Failure mode |
|---|
| Core | 9 um or 50 um | Doped silica | Carries the light | Bend loss, high attenuation |
| Cladding | 125 um | Silica | Confines light | Cracks, reflection lost |
| Coating | 250 um | Acrylate | Abrasion barrier | Wrong strip length |
| Tight buffer | 900 um | PVC or LSZH | Handling and crimp | Clamp crush |
| Jacket | 2 to 3 mm | PVC or LSZH | Cable protection | Rodent and crush damage |
Bend Radius and Polish: Two Costly Confusions
Bend loss and connector loss are the two ways a fiber run degrades without breaking. Both trace back to which layer the installer treated as the reference surface.
Bend Radius Practice
Long wavelength light escapes first when a bend tightens, so a run that tests clean at 1310 nm can still fail at 850 nm on multimode. Keep 30 mm as a working minimum for a 900 um buffered cord and never clamp below 15 mm.
Polish Geometry
PC and UPC ferrules are polished flat or slightly domed, while APC is angled at 8 degrees to suppress reflection. An APC endface mated to a UPC endface leaves an air gap and a reflection that ruins return loss, whatever the cladding measures.
Two Field Cases
Neither link was broken, and neither fault was in the glass.
A Data Hall Patch Panel
A 900 um buffered cord was clamped at a 6 mm radius behind a panel to clear a door. Insertion loss rose by 2 dB on two links within a month, and the cause was bend loss rather than the connectors. Re-routing at a 30 mm radius cleared both.
A Field Termination Batch
An installer stripped a 250 um coating and mistook the remaining layer for the buffer, then cleaved at the wrong length. Every connector in the batch showed high loss. A strip length gauge and a 125 um verification fixed the process.
Frequently Asked Questions
Is cladding the same as the coating?
No. Cladding is the 125 um glass layer that reflects light back into the core. The coating is a 250 um polymer applied over the glass for abrasion and moisture protection. They are different materials with different jobs.
What is the cladding diameter of multimode fiber?
125 um, the same as singlemode. Only the core changes: 50 um for OM3 and OM4, 62.5 um for older OM1. That shared cladding is why one connector and one cleaver serve both types.
Does cladding size affect bend radius?
Indirectly. The 125 um glass sets the minimum bend for bare fiber at about 10 mm, while the 900 um buffer raises the practical minimum to about 30 mm. Quoting the coating dimension gives a radius that is far too tight.
Why does an APC connector fail on a UPC port?
The 8 degree angled endface cannot mate flat against a domed endface, so an air gap remains at the junction. Reflection rises and return loss fails, which shows up as link instability rather than a clean loss of signal.
Can I strip fiber down to the cladding?
Yes for splicing and termination, where the coating is removed to expose bare 125 um glass. The glass must then be cleaned, cleaved and protected, because bare cladding has no abrasion resistance at all.
Related resources: fiber optic glass core and cladding; tight buffered fiber cable; multimode fiber distance