Every cable carries a number: 60, 75, 90, 105, 125. It is printed on the jacket, quoted in the datasheet and argued about in every overload conversation. Most people read it as a working temperature — the level the cable can sit at and be fine.
It is not that. The number is the output of a laboratory aging program, expressed as an index, and it says something narrower and more useful than "this cable is good at 90 degrees."
The rating came out of a chemistry paper
Insulation does not wear out the way a bearing wears out. It reacts with its environment, and the reaction runs faster when it is hot. That sounds like a loose analogy until you follow it properly, and the person who followed it properly was Thomas Dakin.
His 1948 paper, "Electrical Insulation Deterioration Treated as a Chemical Rate Phenomenon," set out the basis for interpreting physical tests of thermal aging and for applying those results to predicting deterioration in service. The argument is stated in the abstract: because the physical changes observed during thermal aging are the result of internal chemical changes in the organic material, the theory of chemical reaction rates can be applied to the analysis of aging data.
That single move is why a temperature rating is an extrapolation rather than a measurement. You cannot run a cable for forty years to find out what happens. You can heat samples well above their intended operating temperature, watch a property change, fit the change to a reaction-rate law, and read the long-term behavior off the curve. The published paper has accumulated several hundred citations, and the approach it established is still the basis of the method used today.

How a temperature class is produced: high-temperature aging, measurement of a diagnostic property, rate analysis, and extrapolation to a temperature index
Three numbers come out of the method, and only one gets printed
The international method for this work is the IEC 60216 series, and its general part states its own purpose precisely. It gives principles of test procedures to evaluate the thermal endurance of electrical insulating materials and simple combinations of them, describes the conditions to be observed during the tests, and shows the basic analysis methods to derive the temperature index, the relative temperature index and the halving interval from the test results.
Three named quantities, from one aging program:
Quantity | What it is |
|---|
Temperature index | The temperature at which the material reaches the chosen end-point in the chosen reference time |
|---|
Relative temperature index | The same figure for a material judged against a reference material |
|---|
Halving interval | The temperature increment that halves the time to the end-point |
|---|
The printed number on a jacket is the temperature index stripped of everything that qualified it. The reference time, the end-point and the diagnostic property measured are all still there in the test report, and none of them travel onto the jacket.
It is worth knowing how the indices are actually determined, because it explains why the answer arrives as a single figure. One part of the series sets out the aging mechanisms and the diagnostic procedures; another determines the indices using a fixed time frame method. In other words, the method fixes how long you age the samples, decides which property you will watch, and then reports the temperature that produces a defined amount of change in that time. Change the end-point and you change the index.
Two datasheets, the same index, different meanings
The index is a single number, but it is produced from four choices: the end-point, the reference time, the diagnostic property, and the test conditions. Change any of them and the number changes, which is why two suppliers can quote the same 90 degrees for genuinely different materials and both be accurate.
The method’s own documentation acknowledges how awkward the data usually is. Its general part gives explicit attention to test data that do not completely satisfy the requirements of linearity and dispersion of the thermal endurance relationship — a polite way of saying that real aging curves bend, scatter and occasionally refuse to behave like a straight line on the Arrhenius plot. The published method exists to handle that, but the handling involves judgment, and judgment is not visible in a catalog entry.
The practical consequence for a buyer is narrow and easy to apply. Comparing two temperature indices is only meaningful when the end-point and the reference time match. If they do not, the two numbers are not the same quantity. Ask for the test report rather than the index, and read the end-point and the reference time off it before comparing anything.
Aging is cumulative, which is why overloads cost service life
A reaction-rate law describes a rate, not a threshold, and a rate integrates.
If deterioration is a chemical process running faster at higher temperature, then the damage is the integral of that rate over time. A cable does not get a fresh allowance every morning. Hours spent running hot are hours spent, and they come out of the same account as the hours spent at ordinary temperatures.
What happens in service | What it does to the account |
|---|
Sustained operation at the rated temperature | Consumes service life at the rate the index implies |
|---|
Periodic overload and hot spots | Consumes life faster during those periods; the accumulation does not reset |
|---|
Running below the rating, in a cool and dry location | Consumes it slower, which is the only way the account ever grows |
|---|

Schematic curve showing time to the end-point falling as temperature rises, with the temperature index marked on the axis
This is the mechanical reason a cable that has never once exceeded its rating can still fail early. It has been living at a higher average temperature than the designer assumed — in a bundled raceway, under insulation, in a hot cabinet — and the state of the insulation is the sum of all of it.
Heat is not the only thing aging the insulation
Treating this as a temperature-only question is the other half of the misunderstanding. The insulation literature models endurance under multiple stress conditions rather than one, and the reason is that temperature is not the only reaction running.
Studies of thermally accelerated aged samples describe degradation as a combination of oxidation and thermal processes. Oxidation depends on oxygen availability, which means a hot cable in air and a hot cable sealed under a jacket are not aging at the same rate even at the same temperature. Voltage stress has its own endurance relationship, which is why the models pair the exponential temperature law with an inverse-power voltage law rather than pretending one covers both.
In the field, the list of things that shorten insulation life is longer than temperature:
- Oxygen and ozone, wherever the surface is exposed to them
- Ultraviolet light on outdoor jackets
- Moisture, both as a hydrolysis reaction and as a driver of water trees in solid dielectric
- Electrical stress, especially at voids, contamination and terminations
- Mechanical stress from bending, flexing and vibration
A jacket qualified at 90 degrees in a dry oven is not automatically qualified for 90 degrees in sunlight, or underwater, or in a flexing application. Those are separate qualifications, and each of them is a separate set of tests.

Which stresses age the insulation, and which property each one attacks
What this means when you specify or buy cable
Four practical consequences follow.
Ask what the number is qualified for. A temperature index is a material classification. It is not a warranty of a service life at that temperature, and two cables with the same printed figure can have different reference times, different end-points and different diagnostic properties behind it.
Treat service life as a separate claim from the rating. When a product standard quotes a service life — the kind of multi-decade figure that appears in solar and outdoor cable specifications — it is making a claim about a defined test regime, not a consequence of the temperature class. Where a supplier offers a long life figure, the useful follow-up question is which standard and which test produced it.
Do not spend the allowance twice. The rating assumes a thermal history. Installing at the rating in a hot, enclosed, bundled route and then planning for occasional overloads is drawing on the same account from both ends.
Check the other qualifications against the actual route. If the cable will see sunlight, water, continuous flexing or chemical exposure, the temperature index is not the binding constraint and asking only about it will miss the one that matters.
FAQ
Does a 90 degree cable mean it can run at 90 degrees continuously?
It means the insulation qualified to a temperature index of 90 degrees in a defined standard test. That is a statement about the material’s thermal endurance under those test conditions, not a promise of indefinite service at that temperature. Sustained operation at the index consumes service life at the rate the test method implies.
Why do insulation failures not show up in electrical tests?
Because aging is a chemical change in the material, and the method measures it through diagnostic procedures rather than through conductivity. The cable keeps carrying current long after the insulation has lost the mechanical and dielectric properties it was specified for, which is why a routine electrical test is a poor indicator of accumulated thermal age.
What is the halving interval?
It is a number derived from the same aging test as the temperature index: the temperature increment that halves the time to the chosen end-point. It is a result of the test, not a universal constant, so it should be quoted from a specific material’s data rather than assumed.
Is temperature the main cause of insulation failure?
It is the best-understood one, and the one with a formal extrapolation method behind it, but the endurance literature models insulation under multiple stresses together. Oxidation, moisture, ultraviolet exposure, electrical stress and mechanical flexing each have their own effect, and in many outdoor and industrial routes one of those is the real limit.
Conclusion
The number on the jacket is the visible end of a method. Samples were aged at high temperatures, a diagnostic property was measured, a chemical rate law was fitted, and a temperature index was read off the extrapolation. That is a much better-founded claim than "it works at 90 degrees," and it is a much narrower one.
Use it as what it is: a qualification of the material, one line of evidence about one stress, and the starting point for the question that actually decides the outcome — what else is this cable going to be exposed to, and for how long.
Specifying cable for a real service life
ZONG Cable builds HDMI, USB, network, patch cord, fiber and communication cable, and specifies jacket and insulation materials against the temperature class and the environment the route actually presents rather than a single printed figure. If you are working through a thermal or environmental qualification, send us the conductor size, the continuous temperature, the ambient conditions and how long the installation has to last, and we will tell you which construction covers it — including when the honest answer is that the cheaper material is sufficient. The range sits under cable, the electrical and dimensional routines are on our test and inspection page, and OEM support covers how drawings and quantities are quoted.
Sources
- IEC 60216-1:1990, Guide for the determination of thermal endurance properties of electrical insulating materials, Part 1: General guidelines for aging procedures and evaluation of test results, scope statement. https://ccn-scc.ca/standardsdb/standards/2035360
- BS EN IEC 60216-6:2022, Electrical insulating materials. Thermal endurance properties. Determination of thermal endurance indices (TI and RTI) of an insulating material using the fixed time frame method. https://www.mystandards.biz/run/print.html?cu=bseniec/60216-6-2022-tc/10.2.2023
- T. W. Dakin, Electrical Insulation Deterioration Treated as a Chemical Rate Phenomenon, Transactions of the American Institute of Electrical Engineers, 1948. https://www.semanticscholar.org/paper/Electrical-Insulation-Deterioration-Treated-as-a-Dakin/4ae07eb45856ba00b12dbd8afbe52d914f752e82
- L. Simoni, A General Approach to the Endurance of Electrical Insulation under Temperature and Voltage, IEEE Transactions on Electrical Insulation, 1981. https://www.semanticscholar.org/paper/A-General-Approach-to-the-Endurance-of-Electrical-Simoni/87d5f14f2e06601aed0d0ddae9c434c61bbf12fc
- T. Saha et al., Investigating the effects of oxidation and thermal degradation on electrical and chemical properties of power transformers insulation, 1999. https://www.semanticscholar.org/paper/Investigating-the-effects-of-oxidation-and-thermal-Saha-Darveniza/6818f3f9adb9d79e5920c5fde235e0366e079a07
- M. Choudhary et al., A Review of Aging Models for Electrical Insulation in Power Cables, Energies, 2022. https://www.semanticscholar.org/paper/A-Review-of-Aging-Models-for-Electrical-Insulation-Choudhary-Shafiq/93954a20daa86be458cf98111d7ea7366f700362
- ZONG Cable range. https://zh-zong.com/cable/