Cat7 Cable: The Connector Problem
Quick answer / TL;DR: Short answer: Cat7 gives no reach advantage over Cat6A at 10G, and its specified connectors are not RJ45. Most Cat7 sold is terminated with shielded RJ45, which places it outside the standard. Specify Cat6A for 10G, or Cat7 only where a client names it and the connector arrangement is agreed.
One category, three axes: shielding, conductor and jacket create the SKU.Cat7 is rated to 600 MHz with shielding on every pair plus an overall braid. It performs well and is rarely specified, for a specific reason.
The specification calls for GG45 or TERA connectors, which do not fit RJ45 ports.
What It Is
| Parameter | Cat7 | Cat6A |
|---|
| Bandwidth | 600 MHz | 500 MHz |
| 10G distance | 100 m | 100 m |
| Shielding | S/FTP typical | Optional |
| Connector | GG45 or TERA | RJ45 |
The reach is identical, so the only reasons to choose Cat7 are interference and a written specification.
Practical Constraints
- Stiffer cable, larger bend radius
- Termination takes about twice as long
- Requires bonded panels
- Limited connector availability
- Not a common horizontal standard
The termination time is a real cost that rarely appears in a cable price comparison.
Real-World Applications
A broadcast facility with dense power cabling may specify S/FTP for immunity. An office at 10G uses Cat6A and certifies without shielding.
Standards and Verification
| Reference | Relevance |
|---|
| ISO/IEC 11801 | Class F |
| IEC 61156 | Cable construction |
| IEC 60603-7 | RJ45 interface |
Connector requirements are defined in ISO/IEC 11801 and are not reproduced here. Check the standard.
References
- ISO/IEC 11801-1, Generic cabling
- IEC 61156-5, Symmetrical pair/quad cables
- IEC 60603-7 series, 8-way connectors
Practical Notes
Confirm the connector type in writing before ordering Cat7. Discovering the mismatch at installation is expensive.
Related reading: cat6a cable — blogs/news/cat6a-cable
Related reading: cat6 vs cat7 cable — blogs/news/cat6-vs-cat7-cable
Frequently Asked Questions
Does Cat7 reach further?
No. Same 100 m at 10G.
Does it use RJ45?
Not in the specification.
When specify Cat7?
Only against a written requirement.
Is it harder to install?
Yes. Stiffer and slower to terminate.