EtherCAT Cable for Servo Axis: Communication Is the Easy Half
Quick answer / TL;DR: Short answer: use a hybrid cable where the axis moves and cable count matters, and separate cables where the run is fixed or the drive current is high. In both cases the flex rating, the bend radius and the shield bonding decide the service life, and the EtherCAT pair must remain shielded from the motor conductors.
Industrial cable adds four decisions to the office SKU: oil, flex, EMI and connector.A servo axis needs two things from the cable that reaches it: the EtherCAT link that carries the command, and the power that drives the motor. Everything else in the selection follows from whether those share a jacket.
The communication side is a shielded twisted pair with modest electrical demands. The motor side carries switched current with high dv/dt, which is why combining them is a genuine engineering decision rather than a packaging preference.
This article covers the hybrid versus separate decision, the flex life requirement that dominates both, and the grounding detail that decides whether either works.
The EtherCAT pair is a 100 ohm shielded twisted pair running at 100 Mbps. It is electrically modest, and its main vulnerability is noise rather than attenuation.
The motor conductors carry switched current, and their edges are the noise source. Whether they share a jacket with the communication pair is the central question.
The Two Arrangements
| Aspect | Hybrid cable | Separate cables |
|---|
| Cable count | One per axis | Two per axis |
| Noise separation | By internal shielding and geometry | By physical distance |
| Flex life | One cable to qualify | Two cables, each simpler |
| Field termination | Requires matched connectors | Standard connectors |
| Repair | Whole assembly replaced | One cable replaced |
Hybrid cable wins on cable count and on drag-chain volume, which matters on a machine with many axes in a confined chain. It loses on repair, because a damaged communication pair means replacing the assembly.
Separate cables win on noise separation and on serviceability, which matters where the run is fixed and the drive current is high.
Where Flex Life Dominates
- Specify cycle count with bend radius and travel length, because a cycle rating without geometry is not usable
- Qualify the whole assembly, since a hybrid cable's flex life is set by its stiffest element
- Keep the drag-chain bend radius within the cable's rating, because a radius violation consumes life silently
- Separate the fixed and moving portions of the run, and use a strain relief at the transition
- Record the cycle count the machine is expected to run, which turns the rating into a maintenance interval
Real-World Applications
A six-axis robot uses hybrid cable per axis because the drag chain has no room for twelve cables. The assembly is qualified as a unit and replaced as a unit.
A gantry with two axes over a long travel uses separate cables because the drive current is high and the communication pair benefits from physical distance.
A machine tool keeps the EtherCAT run fixed in the cabinet and uses a separate drag-chain cable only for the moving axis. The split follows the motion rather than a house standard.
A retrofit adds an axis to an existing drag chain. The remaining space decides between hybrid and separate more often than the electrical argument does.
Standards and Verification
EtherCAT is specified in IEC 61158 and IEC 61784-2. Cable performance follows ISO/IEC 11801 and TIA-568, industrial installation practice follows IEC 61918, and drive EMC guidance comes from the IEC 61800 series.
Verification should include a channel certification for the communication pair, shield continuity end to end, and a flex qualification for the assembly at the specified radius and travel.
For hybrid assemblies, verify that the motor conductors are shielded individually or as a group, and that the EtherCAT pair's shield is separate from the motor shield. A shared shield couples the noise into the signal.
Grounding and the Fourth Conductor
A servo axis needs a protective earth that is not the cable shield. Confusing the two is a common and dangerous error.
The shield carries noise current and must be bonded at both ends. The protective earth carries fault current and must meet the installation's earthing requirement.
In a hybrid cable these are separate conductors, and the assembly drawing should show which is which.
The Connector Is Part of the Axis
Servo connectors are frequently specific to a drive family, which makes the cable a qualified assembly rather than a commodity.
That qualification is the reason a cheaper equivalent is rarely equivalent: the connector, the shield termination and the flex rating are qualified together.
Record the assembly part number against the axis, so the replacement is the qualified one.
Where a drive family changes, the cable assembly usually changes with it. Planning for that at the design stage is cheaper than discovering it during a drive replacement.
Keep the old assembly part numbers after a drive upgrade. The information is worth nothing later and costs nothing to retain now.
Related reading: EtherCAT cable selection — blogs/news/ethercat-cable
Related reading: Ethernet cable separation from power — blogs/news/ethernet-cable-separation-from-power
Related reading: Cat6A industrial jacket — blogs/news/cat6a-industrial-jacket
A hybrid cable with a shared shield is a communication cable wrapped around its own noise source. Check the shield arrangement before the flex rating.
Frequently Asked Questions
Is hybrid cable better than separate cables for a servo axis?
It depends on the application. Hybrid saves space and cable count in a drag chain; separate cables give better noise separation and easier repair.
What flex rating should a drag-chain EtherCAT cable have?
A stated cycle count with the bend radius and travel length. Without those conditions the number cannot be applied to a machine.
Can EtherCAT share a jacket with motor power?
Yes, in a properly constructed hybrid cable with separate shields. A shared shield couples the motor noise into the communication pair.
Does the EtherCAT pair need a different cable for servo use?
No. It is a standard 100 ohm shielded pair. What changes is the mechanical construction and the shielding arrangement around the motor conductors.
Sourcing cables for a project, a store, or a private-label line? Contact our B2B sales team for specifications, certification evidence, and volume terms – FOB and CIF options available. Request a quote or sample.